Super intelligent Wind Solar Hybrid Controller / Wind And Solar Hybrid Controller
Super-intelligent wind/solar hybrid controller is a new type of special high performance control device for new energy application which is designed on the basis of ultra high performance controller. It contains many years of application experience (such as waterproof, dustproof, salt spray, wiring error, wind resistance limit control of Wind turbines, energy management etc.), it has done to ultimate no matter it applied to the charging control or street light control. In order to meet variety of applications, the controller adopts a hierarchical and modular structure, all functions can be achieved with different functional plates according to actual application, and it is convenient for rapid customization and application.
Brief Functions:
RS232 communication
Specification:
Model | CXF600w-24V off-grid | CXF600W-48V off-grid | ||
Battery parameters | ||||
Applied battery voltage | 24V | |||
Battery protect method | Reverse connection protection (do not burn any components, with voice prompt); over voltage protection, under voltage protection (for street light and such kind of load) | |||
Voltage at the over voltage protection point | 29.0V±0.2V | 58.0V±0.3V | ||
Voltage at the over voltage recovery point | 27.5V±0.2V | 55.0V±0.3V | ||
Voltage at the under voltage protection point | 21.0V±0.2V | 42.0V±0.3V | ||
Voltage at the under voltage recovery point | 23.0V±0.2V | 46.0V±0.3V | ||
Battery temperature compensation | 5mv/℃/2V (settable) (optional component) | |||
Wind turbines input parameters | ||||
Rated power of applied Wind turbines | 600W/24V | 600W/48V | ||
Rated power of the terminal | 30A dc (after rectification) | 15A dc (after rectification) | ||
Max. input current of the terminal | 40A dc (after rectification) | 20A dc (after rectification) | ||
The default speed of the Wind turbines generation with limited speed | 500 Rpm (settable) | |||
The default current of the Wind turbines generation with limited current | 30A (settable) | 15A (settable) | ||
Wind turbines protection method | over rev protection, over current protection, induction lightening protection | |||
Unloading method | PWM stepless high-frequency soft unloading (built-in) | |||
MPPT function | Boost MPPT model ( automatic tracking or 5 segments curve tracking) | |||
Input current of MPPT channel | 12A | |||
PV input parameters | ||||
Rated input current of applied PV | 550W/24V(standard) | 1100W/48V(standard) | ||
Rated input current of terminal | 15A(standard) | |||
Charging voltage drop | <0.2V | |||
PV protection methods | Reverse connection protection (voice prompt) | |||
Unloading method | Open circuit unloading | |||
Discharge the output port parameters | ||||
output | 2 outputs | |||
Current of each output | 12A | |||
Output protection methods | Over current protection (15A/30sec. 18A/0.4sec.), short-circuit protection (current > 150A) | |||
Output control methods | light control, time control, reverse output, PWM output (250HZ, only the 2nd output has it) | |||
Others | ||||
Auxiliary function | Monitor of air temperature inside controller, temperature of unloading parts and Wind turbines MPPT components, and also the monitor of control terminals installed on the inversion (with voice prompt) | |||
Display mode | Liquid crystal (LCD) display | |||
Communication mode | RS232(5V electrical level)/RS485 (standard) | |||
Displayed parameters | Wind turbines input voltage/current/power/generated energy/rev/unloading current | |||
Power consumption in standby mode(screen backlight closed) | About 20ma /24V system | |||
Operating mode | 3M foil key operation (4 keys) | |||
Working temperature / humidity range (environment) | -40~+80℃/20~85%RH(non condensing) | |||
Protection grade | IP41 | |||
Controller size (L*W*H) | 175mm*148mm *84mm | |||
Net weight | 1.8KG | |||